PORTABLE - 3kVA
Genset Model |
CC3AS |
||
DG Prime Rating at rated rpm | 3 kVA |
||
Frequency |
Hz |
50 |
|
Power factor |
lagging |
0.8 |
|
Voltage |
V |
230 (1Ø ) |
|
Governing class ( As per ISO 8528 Part-V) |
G2 |
||
Noise level |
dBA |
<70 |
|
Fuel Consumption* | At 100 % Load |
Ltrs/Hr |
1.0 |
At 75 % Load |
0.75 |
||
At 50 % Load |
0.6 |
||
Fuel Tank Capacity |
Ltrs |
13 |
|
Overall dimensions of genset (L x W x H)^ |
mm |
920x560x920 |
|
Dry weight of genset with canopy (approx..)^ |
Kg |
180 |
|
Wet weight of genset with canopy (approx..)^ |
Kg |
190 |
|
Electrical Battery starting voltage |
Volts-DC |
12 |
|
ENGINE | |||
Engine Model |
|
CC306 G1 |
|
Rated output (Prime Continuous rating as per ISO 8528-1) |
kW |
3.38 |
|
HP |
4.60 |
||
No. of cylinder |
Number |
1 |
|
Cubic capacity |
CC |
306 |
|
Rated Speed |
RPM |
3000 |
|
Aspiration |
NA/TC/TA |
NA |
|
Lube Oil change period |
hrs. |
200 |
|
Lube oil Sump Capacity |
Ltrs |
1.1 |
|
ALTERNATOR | |||
Insulation Class |
Class H |
||
Alternator Efficiency (at 100% load) 0.8 pf** |
% |
74 |
|
Max Voltage Dip at Full Load 0.8 pf Lag |
sec |
< 20 % |
|
Max Time to build up rated voltage at Rated RPM | < 5 sec provided engine reach the rated speed |
For intermediate ratings, kindly contact nearest KOEL office
Notes
^ Tolerances Apply
*With 0.845 Specific Gravity of diesel ( 5 % Tolerance )
** Efficiency of Alternator as per standards IS 4722 and IEC 34-1 For Site Conditions other than standard operating conditions consult KOEL for available prime power.
‘Prime power’ is designed for Unlimited hours, as compared to 'Emergency stand-by' designed for 200 hours in a year. Prime rated Gensets also permit 10% temporary overloading. Users need to carefully select the Genset rating to meet their requirement. KOEL offers Prime power as standard offer. Contact KOEL for stand-by ratings.
Engine capacity (cc) plays a vital role in Genset performance. Higher engine capacity leads to a robust and stable Genset performance.
Higher engine capacity also enables Genset to respond quickly & positively to sudden load additions.

1. Canopy
2. Controller
3. Engine
4. Alternator